Installation and calibration notes for pressure / DP transmitters
Direct answer: Most field reading errors come from installation, not the sensor: impulse line routing, manifold sequence, static pressure, condensate pots and calibration scope. Check these before replacing a transmitter.
Impulse lines
Keep a consistent slope to avoid gas pockets in liquid service and liquid pockets in gas service. Keep both sides at the same temperature where possible.
Three-valve manifold sequence
Follow the manufacturer's sequence for equalising and isolating; incorrect operation can apply over-range pressure to one side.
Steam service
Add condensate pots on both sides and keep the liquid levels equal. Account for static pressure effect on DP readings.
Remote seals
Capillary temperature effect and response lag add error; install both sides at the same elevation and exposure, and include this in the error budget.
Calibration
Follow the applicable procedure and the loop error budget. A manufacturer's long-term stability figure is drift, not a calibration interval.